Key Features

✓ EN161 gas safety shut-off valve
✓ DN300 (12") PN16 flanged connection
✓ 2/2 way normally closed
✓ Manual reset safety operation
✓ Dual-shutter pressure compensation system
✓ Fail-safe closed on power loss
✓ Requires manual reopening after shutdown
✓ Maximum operating pressure 600 mbar
✓ Optional 6 bar EVRM-6NC version
✓ Kvs flow factor 1020 m³/h
✓ Closing time under 1 second
✓ Integrated 600μm filter
✓ G1/4 pressure monitoring ports
✓ G1/8 connection for optional PCS912 closed-position switch
✓ Continuous duty 100% ED

DN300 PN16 Gas solenoid valve EN161 600mBar Manual Reset

£4,763.24 incl. VAT £3,969.37 ex. VAT

-63% Was £13,010.10 incl. VAT

Brand: Elektrogas

Model: EVRM-NC912

Stock: 3 in stock

Read Full Description

Description

DN300 PN16 Gas Safety Shut-Off Valve Manual Reset Elektrogas EVRM-NC912


The Elektrogas EVRM-NC912 is a DN300 (12") PN16 flanged, 2/2 way normally closed manual-reset gas safety shut-off solenoid valve designed for automatic isolation of natural gas, LPG, air and compatible non-aggressive gases.

Designed for gas detection systems, burner installations, boilers, gas trains and other gas-consuming equipment, the EVRM-NC912 provides fail-safe gas isolation when connected to gas leakage detectors, safety thermostats, carbon monoxide alarms or other safety control systems.

The DN300 valve incorporates a dual-shutter pressure compensation system to assist manual resetting. Energising the coil does not automatically reopen the gas supply. The reset control must first be operated to equalise the pressure across the valve before it can be moved fully into the open position.

Key Features

✓ EN161 gas safety shut-off valve
✓ DN300 (12") PN16 flanged connection
✓ 2/2 way normally closed
✓ Manual reset safety operation
✓ Dual-shutter pressure compensation system
✓ Fail-safe closed on power loss
✓ Requires manual reopening after shutdown
✓ Maximum operating pressure 600 mbar
✓ Optional 6 bar EVRM-6NC version
✓ Kvs flow factor 1020 m³/h
✓ Closing time under 1 second
✓ Integrated 600μm filter
✓ G1/4 pressure monitoring ports
✓ G1/8 connection for optional PCS912 closed-position switch
✓ Continuous duty 100% ED

Technical Specification

Model: Elektrogas EVRM-NC912
Function: 2/2 way normally closed with manual reset
Operation: Manual reset, direct acting gas safety shut-off valve with dual-shutter pressure compensation
Connection: DN300 (12") PN16 flange
Maximum pressure: 0.6 bar / 600 mbar
High-pressure option: EVRM-6NC912, maximum 6 bar
Kvs flow factor: 1020 m³/h
Closing time: <1 second
Media: Air and non-aggressive gases in gas families 1, 2 and 3 according to EN 437
Body: Aluminium alloy
Seals: NBR-based rubber certified for gas according to EN 549
Filter: Integrated 600μm metal mesh
Pressure monitoring: G1/4 pressure gauge connections
Position indication: G1/8 connection included for optional PCS912 closed-position indicator switch
Standard voltage: 230V AC 50/60Hz
Voltage options: 110V AC 50/60Hz, 24V AC/DC or 12V AC/DC
Voltage tolerance: -15% to +10%
Power consumption: 12 W
Duty: Continuous service, 100% ED
Protection: IP54
Electrical connection: Terminal box
Coil thermal resistance: Class F

Manual Reset & Pressure Compensation Operation

When de-energised, an internal spring holds the valve disc closed and prevents gas flow.

Applying electrical power to the coil does not automatically open the valve. To restore gas flow, the coil must first be energised.

The DN300 EVRM-NC912 incorporates a dual-shutter pressure compensation system. To reset the valve, pull the reset control through the first stage and wait for the inlet and outlet pressure to equalise. The control can then be pulled completely to the fully open position.

Once manually reset, the valve remains open while electrical power is maintained.

If electrical power is interrupted by a gas detector, safety thermostat, emergency control or power failure, the valve closes rapidly in under one second. When power is restored, the valve remains closed.

The cause of the shutdown must therefore be investigated and cleared before the valve is manually reset and the gas supply restored.

Gas Safety Applications

The EVRM-NC912 is suitable for safety isolation applications including:
✓ Gas leak detection systems
✓ Natural gas installations
✓ LPG installations
✓ Gas-fired burners
✓ Boilers and heating equipment
✓ Industrial gas trains
✓ Safety thermostat systems
✓ Carbon monoxide alarm systems
✓ Emergency gas shut-off systems

Pressure Gauge & Position Indication Connections

G1/4 pressure gauge connections are provided for connection of compatible:
✓ Pressure gauges
✓ Pressure switches
✓ Gas leakage testers
✓ Other gas monitoring equipment

A G1/8 connection is also provided for fitting the optional PCS912 mechanical closed-position indicator switch.

Optional Versions & Accessories

6 Bar Version: EVRM-6NC912 version available for operating pressures up to 6 bar.
PCS912 Closed Position Switch: Optional mechanical closed-position indication switch.
Normally Open Version: EVRM-NA912 manual-reset normally open version available.
Biogas Version (J): Special version available for biogas, free of ferrous metals with FPM sealing.
ATEX Version: EVRM-NC912X explosion-protected execution available for Zones 2 and 22 according to ATEX 2014/34/EU.
110V AC: Alternative supply voltage.
24V AC/DC: Alternative supply voltage.
12V AC/DC: Alternative supply voltage.

Certifications & Compliance

EN161 Class A Group 2 gas safety shut-off valve
Pressure Equipment Directive 2014/68/EU – CE Reg. No. PED/0497/895/07
ATEX 2014/34/EU when specified
Electromagnetic Compatibility Directive 2014/30/EU
Low Voltage Directive 2014/35/EU
RoHS II 2011/65/EU

Installation Notes

The valve may be installed with the coil vertically or horizontally, but must not be installed upside down.

For installation in vertical pipework, gas flow must be from bottom to top.

A gas filter should be installed upstream of the valve, and the installation location must be protected from rain, water splashes and dripping water.

Leak and functional testing should be carried out after installation in accordance with applicable regulations and the manufacturer's instructions.

Related Products & Categories



Replacement Elektrogas Solenoid Coils

Position Switches & Power Knock Off Buttons
View Technical Specification

Technical Specification

Brand: Elektrogas

Model: EVRM-NC912

Width: 700.00 mm

Height: 786.00 mm

Depth: 460.00 mm

Weight: 99.00 kg

Valve / Product Type: Safety Shut Off, Solenoid Valve

Body Material: Aluminium

Voltage: 12vDC, 24vDC, 24vAC, 110vAC, 230VAC

Port Size: 12 inch Flange DN300

Function: 2/2 Failsafe Closed

Operation: Assisted Lift

Pressure: 0.02 Bar (20 mBar), 0.1 Bar (100 mBar), 0.2 Bar (200 mBar), 0.3 Bar (300 mBar), 0.4 Bar (400 mBar), 0.5 Bar (500 mBar), 0.6 Bar (600 mbar), 0.7 Bar (700 mBar), 0.8 Bar (800 mBar), 1 Bar, 1.2 Bar, 1.3 Bar, 1.4 Bar, 1.5 Bar, 1.6 Bar, 2 Bar, 2.5 Bar, 3 Bar, 3.5 Bar, 4 Bar, 4.5 Bar, 5 Bar, 5.5 Bar, 6 Bar

Seals: NBR, FKM (Viton)

Approvals:: IP65, EAC, EN161

Media: Gases (Non Aggressive), Gases (Slight Acid/Alakli), Natural Gas

Options required: Manual Reset, Position Feedback Closed

Orifice: 300mm

We use a few optional cookies to see how our adverts and site perform. Details